2.3. CHIMNEY HEIGHT DIMENSIONING AND EXTENSIONS
The Modular Chimney’s maximum structural height is 30
metres. By structural height we mean the chimney’s own height.
Remember to account for the E3 regulations of the Finnish
building code or equivalent regulations in Your country of
residence regarding the height of the chimney with regard to the
highest part of the roof!
When the chimney rests with a non-insulated connection pipe
on top of the replace, its maximum total structural height
counting the connection pipe is 5 metres.
The replace’s structure also aects the chimneys maximum
height (see chapter 2.1 Foundation). If the chimney includes a
pipe bend element KC-17, the maximum height above it is 5 metres.
Remember the bracing. See chapter 2.9.9 Pipe bend element KC-17.
The chimney’s maximum height is determined by the roof’s inclina-
tion and shape, the replace’s draught requirements and environ-
mental factors (e.g. location in a valley, on a slope, next to a large
tree etc.). This height must be conrmed with the responsible of-
cials and the replace’s manufacturer. At times it can happen that
the chimney’s minimum height will not produce adequate draught
conditions. In such a case it is easy to extend the chimney’s height
by adding an extension segment beneath the KC-32 end cap. Check
for the need for additional bracing (See chapter 2.2 Supports).
2.3.1. INSTRUCTIONS FROM THE E3 BUILDING CODE
Attn.! When the chimney does not pierce the roof close to the
top, add 10 cm to height for each metre of roof (80, 90, 100,
110…). (Illustration 2)
2.4. CHIMNEY HEIGHT ADJUSTMENT
The basic height comes from a suitable number of modules.
This is then ne-tuned as follows:
The non-insulated connection pipe or the support segment
(KC-03) is cut down to the required length using a metal saw
or an angle grinder. The cut end must be exactly perpendicular
to the length of the segment. The non-insulated connection
pipe can be extended with a non-insulated extension pipe.
A chimney resting on the oor may be raised for instance with
a cast concrete block beneath it, if possible, or some other suf-
ciently stable support. The chimney must not be extended at
its upper end with a mere length of piping.
The support segment (KC-03) can be shortened by cutting the
excessive length o its upper end.
Illustration 2.
Drawing from Finnish E3 building code chimney height in relation with the
roof’s highest point.
1.0 m = non-ammable roong
1.5 m = felt or wood shingle roong
2.3.
2.3.1.
2.4.
Number of needed modules
Total
height
of
chimney
(m)
Starting
element
KC-37
End
cap
KC-32
Exten-
sion
1 m
KC-13
Exten-
sion
0,5 m
KC-14
Exten-
sion
0,25 m
KC-15
Eective
height of
modular
chimney
(mm)
3,00 1 1 3 – 1 3180
3,25 1 1 3 1 – 3430
3,50 1 1 3 1 1 3620
3,75 1 1 4 – – 3930
4,00 1 1 4 – 1 412 0
4,25 1 1 4 1 – 4370
4,50 1 1 4 1 1 4560
4,75 1 1 5 – – 4870
5,00 1 1 5 – 1 5060
5,25 1 1 5 1 – 5310
5,50 1 1 5 1 1 5500
5,75 1 1 6 – – 5810
6,00 1 1 6 – 1 6000
6,25 1 1 6 1 – 6250
6,50 1 1 6 1 1 6440
6,75 1 1 7 – – 675 0
7,00 1 1 7 – 1 6940
7,25 1 1 7 1 – 71 90
7,50 1 1 8 – – 7690